ENGiVAULTEngineering workspace
← All calculators

HVAC

Humid Air Properties

Enter values in the stated units. Example inputs are provided to help you explore the method.

Inputs

Results

Your results will appear here after calculation. Changing an input clears the previous result.

Method & assumptions

  1. Calculate humidity ratio, dew/frost point, enthalpy, specific volume and moist-air density from temperature, relative humidity and absolute pressure.
  2. Supported inputs: −50 to 80 °C, 0–100% RH and 20–120 kPa absolute. Total pressure must exceed saturation vapor pressure at the dry-bulb temperature.
  3. ASHRAE saturation equations use ice at or below 0.01 °C and liquid water above it. RH is relative to that phase; subfreezing RH reported relative to liquid water must be converted before use.
  4. Water-vapor pressure is RH/100 times saturation pressure. W = 0.621945 pv/(p − pv); specific humidity = W/(1 + W).
  5. Enthalpy h = 1000[1.006T + W(2501 + 1.86T)] J/kg dry air, with T in °C and the conventional dry-air/liquid-water zero at 0 °C. It is not enthalpy per kg of moist air.
  6. v = 287.042(T + 273.15)(1 + 1.607858W)/p; total density = (1 + W)/v. Assumes ideal moist air with no liquid droplets or real-gas corrections.
  7. Dew/frost point inverts the saturation equation. Dry air has no finite dew point; results below −100 °C are reported outside the model range. These labels are returned as strings in the API.
  8. Adapted coefficients from MIT-licensed PsychroLib; the numerical inversion, exact zero-humidity behavior and restricted operating domain differ from that library.

Sources